									Purpose: 
									 
									Controls and alerts the high flammable and 
									toxic gases content in the work area  
									 
									Application: 
									Boiler rooms (liquefied and natural gas), 
									industrial, administrative and residential 
									areas 
									 
									Technical specifications: 
  
										
											|   | 
											
											 
											
											SGS-901  | 
											
											 
											
											SGS-902  | 
										 
										
											| 
											 Number 
											of channels | 
											
											 
											
											2
											  | 
											
											 2
											 | 
										 
										
											| 
											 Number 
											of programmable launches | 
											
											 
											
											2
											  | 
											
											 2 | 
										 
										
											| 
											 Type 
											of signal | 
											
											 ‘dry’ 
											contact, 
											
											light, sound  | 
											
											 
											
											‘dry’ contact, 
											
											
											light, sound  | 
										 
										
											| 
											 
											
											              
											Launch values of alarm 
											
											-        
											
											
											for flammable gases, % LCLFP 
											
											
											        
											-        
											
											
											for toxic gases, mg/m3  | 
											
											 1st 
											limit 10 � 5 
											
											2nd limit 
											20 � 5 
											
											
											1st limit 
											1 MAC 
											
											
											2nd limit 
											5 MAC  | 
											
											 
											
											1st limit 
											10 � 5 
											
											
											2nd limit 
											40 � 5 
											
											
											1st limit 
											1 MAC 
											
											
											2nd limit 
											5 MAC
											  | 
										 
										
											| 
											 Explosion 
											protection | 
											
											 
											
											none
											  | 
											
											 
											
											
											1ExibIIC(B)T6(T4)  | 
										 
										
											| 
											 Power 
											supply | 
											
											
											220 V, 50 Hz
											 | 
											
											 
											
											220 V, 50 Hz  | 
										 
										
											| 
											 Communication 
											channel | 
											
											
											4-20 mA | 
											
											 4-20 
											mA | 
										 
										
											| 
											 
											
											
											Work range of 
											temperatures, C� | 
											
											
											From 0 to +50 | 
											
											
											From -20 to +50 | 
										 
									 
									
									The alarm 
									device consists of the control and alert 
									compartment and the probes with 
									electrochemical and thermocatalytic sensors 
									 
									Detectable gases: 
									 
									- toxic: CO, NO2, H2S, SO2, NH3, O2 and 
									others 
									 
									- flammable: methane, propane, butane, 
									acetylene, ethanol, methanol,  
  acetone, hydrogen and others 
									 
									There is a possibility to use probes as 
									separate alarm devices without the control 
									compartment 
									 
									Advantages: 
									 
									- works from 220 V outlet 
									 
									- simple to install and use 
									 
									- long life cycle 
									 
									- small size 
									 
									- high sensitivity 
									 
									- digital output RS-485 
   |